WX900 Integrated Power Distribution Protection Device
+
  • WX900 Integrated Power Distribution Protection Device

WX900 Integrated Power Distribution Protection Device


The WX900 is an advanced microprocessor-based protection and control unit that integrates six functions: protection relaying, metering, switch status display, temperature/humidity control, infrared detection, and intelligent voice prompt.


  • Core Advantages
  • Technical Parameter
  • 1. The WX900 is an advanced microprocessor-based protection and control unit that integrates six functions: protection relaying, metering, switch status display, temperature/humidity control, infrared detection, and intelligent voice prompt.
    2. WX900 series models (L, Y, D, R, T2, T3, J) combine seven protection functions in one device: line protection, transformer protection, motor protection, capacitor protection, incoming feeder auto-transfer, bus-tie auto-transfer, and voltage transformer protection.
    3. As an industry pioneer in China, the WX900 is the first protection device equipped with the independently developed DianHong PHMV1.0 operating system with proprietary intellectual property rights.
    4. Built on a new highly-integrated microcontroller platform with on-chip bus architecture, the device delivers superior anti-interference performance.

  • Rated data

    Error of measurement

    Power consumption

    Adapt to the environment

    Overload capacity

    Insulation withstand voltage

    (1)AC current: 5A/1A
    (2)AC voltage: 100V (rated current Un)
    (3)AC frequency: 50Hz
    (4)Power supply voltage: AC/DC80-264V
    (1)Measured voltage and current: ≤±0.5%
    (2)Active (reactive) power: ≤±0.5%
    (3)Protection current: ≤±3%
    (1)AC current circuit: In=5A, each phase ≤1.0VA; In=1A, each phase ≤0.5VA
    (2)AC voltage circuit: U=Un, each phase ≤0.5VA
    (3)Device complete circuit: normal operation < 6W; Protection action ≤7W
    (1)Normal operating temperature: -10 °C ~ 55 °C
    (2)Limit operating temperature: -25 °C ~ 60 °C
    (3)Storage and transportation: -40°C~70°C
    (1)AC current circuit: 2 times the rated current, continuous operation; 10 times the rated current, allowing 10S; 40 times the rated current, allowing 1S
    (2)AC voltage circuit: 1.2 times the rated voltage, continuous operation
    (1)AC input to ground: greater than 100 megohms
    (2)DC input to ground: greater than 100 megohms
    (3)Input circuit to ground: greater than 100 megohms